Deck stair rules in NSW

Deck stairs in NSW follow Part 11.2 of the NCC Housing Provisions. Here are the riser, tread, landing and handrail numbers.

The short answer

Deck stairs in NSW must have risers between 115 mm and 190 mm high and goings (tread depth) between 240 mm and 355 mm, with twice the riser plus the going (2R + G) between 550 mm and 700 mm. A flight has at least 2 and no more than 18 risers, and the risers and goings must stay constant through the flight. Open risers must not let a 125 mm sphere through, landings must be at least 750 mm long, and a handrail is needed on at least one side where the change in level is 1 m or more. These numbers come from Part 11.2 and Part 11.3 of the ABCB Housing Provisions, part of the National Construction Code (NCC).

Which code applies

NSW uses NCC 2022, currently NCC 2022 Amendment 2, in effect from 29 July 2025. NSW adopts NCC 2025 on 1 May 2027. Stair rules sit in Housing Provisions Part 11.2. Following Part 11.2 meets performance requirement H5P1 in NCC Volume Two. A builder may instead use a Performance Solution that meets the performance requirements. Stairs must also be designed for loads to AS/NZS 1170.1.

Stair dimensions

RuleLimitClause
Riser height115 mm to 190 mmTable 11.2.2a
Going (tread depth)240 mm to 355 mmTable 11.2.2a
2R + G550 mm to 700 mmTable 11.2.2a
Risers per flightAt least 2 and no more than 1811.2.2(1)(a)
Gap in open risersMust not let a 125 mm sphere through11.2.2(1)(d)
Landing lengthAt least 750 mm11.2.5
Landing gradientNot steeper than 1:5011.2.5

Keeping steps even

Risers and goings must be constant through a flight. Adjacent risers or goings may vary by no more than 5 mm, and the largest and smallest in a flight by no more than 10 mm (11.2.2(1)(c)). On a sloping yard this means the bottom step needs a level, solid base so it matches the rest of the flight.

Working out a stair

A worked check using the table, for a deck 900 mm above a level landing pad:

  1. Divide the height into equal risers. Five risers of 180 mm give 900 mm.
  2. Check the riser: 180 mm is inside 115 mm to 190 mm.
  3. Pick a going. With a 260 mm going, 2R + G is 2 x 180 + 260 = 620 mm, inside 550 mm to 700 mm.
  4. Check the risers per flight: 5 is between 2 and 18.

This is the arithmetic only. Real stairs also depend on the ground, the landing, the stringers and the fixings, and Addan sets them out on site.

Doorway thresholds

A doorway threshold more than 230 mm above the surface outside needs compliant steps (11.2.6). This often comes up where a back door sits well above the yard. A deck built up to the door level solves it, or steps are built to the rules above.

Slip resistance

Stair treads must meet slip resistance classes tested to AS 4586 (Table 11.2.4):

SurfaceMinimum class
Treads, dry surfacesP3 or R10
Treads, wet surfacesP4 or R11
Nosing strips, dryP3
Nosing strips, wetP4

Deck stairs outdoors get wet, so the wet surface classes are the ones to plan for. Ask Addan which tread and nosing options meet this for your material.

Handrails and balustrades on stairs

From clause 11.3.5:

  • a handrail is required on at least one side of a stair flight, for its full length;
  • its top must be at least 865 mm above the stair nosings;
  • it must be continuous, with nothing that breaks a handhold, though newel posts are allowed;
  • a handrail is not required where the change in level is less than 1 m.

Where it is possible to fall 1 m or more from the side of the stair, a balustrade is needed as well. On stairs it must be at least 865 mm above the nosings, and openings are measured above the line of the nosings and must not let a 125 mm sphere through. If the balustrade is fixed to the side face of the stair, the gap to the face must not exceed 40 mm. Full details are in deck balustrade rules.

Stairs on exempt decks

A low deck built as exempt development still has to meet the Building Code of Australia deemed-to-satisfy provisions under s 1.16 of the Codes SEPP. The stair rules apply whether or not council approval was needed. See deck council approval in NSW.

Materials for deck stairs

The timber rules for decks apply to stairs too. From WoodSolutions Technical Design Guide 21:

  • framing within 150 mm of the ground should be in-ground Class 1 hardwood or treated to at least H4;
  • posts embedded in the ground should be in-ground Class 1 hardwood or treated to H5;
  • treads, like deck boards, should be above-ground Class 1 or 2 hardwood (with sapwood removed or H3 treated), or timber treated to at least H3.

If a stair has soft timber, loose treads or a moving handrail, have it checked. Stair repairs are work for a licensed builder.

How we build deck stairs

Addan measures the finished deck height and the ground at the stair position, then sets out risers and goings that fit the table and stay even. He builds the landing or base, cuts and fixes the stringers, fits the treads and adds the handrail and balustrade where needed. Wide feature steps, stairs with a landing partway, and stairs on sloping ground are all part of the deck stairs and balustrades work we do. Use the instant estimate for a deck with stairs, or call 0476 217 422 for a free on-site quote.

Common questions

What is the maximum step height for deck stairs in NSW?

The riser must be no more than 190 mm and no less than 115 mm, under Table 11.2.2a of the NCC Housing Provisions.

How deep should deck stair treads be?

The going must be between 240 mm and 355 mm, and twice the riser plus the going must be between 550 mm and 700 mm.

Do I need a handrail on 3 deck steps?

A handrail is not required where the change in level is less than 1 m. Three steps at a typical riser height add up to less than 1 m, but measure your own: once the change in level reaches 1 m, a handrail is required on at least one side.

How many steps can a deck stair have before a landing?

No more than 18 risers in a flight. A landing must be at least 750 mm long and no steeper than 1:50.

Are open risers allowed on deck stairs?

Yes, as long as the gap does not let a 125 mm sphere pass through.

Do deck stairs need to be non-slip?

Treads must meet P3 or R10 for dry surfaces and P4 or R11 for wet surfaces, tested to AS 4586. Nosing strips must be P3 dry or P4 wet.

Written by Addan, licensed carpenter (NSW Licence 391427C) · Updated 20 October 2026. General information only. Every site is different, so ask about yours.